ATS Designers Guide 65
Table 4-11 Mapping zones to access control functions – local addressing.
Passage
Open door
blocked zone
Exit button DOTL Spare
Door 1 1 3 16 2
Door 2 4 6 15 5
Door 3 7 9 14 8
Door 4 10 12 13 11
4.4.3 Advanced Access Control of the ATS1260 DGP
The elevator controller uses 256 inputs and 256 local outputs. They are used to control
the elevators buttons (inputs) and enforcing access rights for the floors (outputs) As the
controller supports 64 floors and 4 elevators, it needs to have 256 inputs and outputs.
There are only 16 inputs on the controller’s board, so additional inputs need to be
provided by expanders – access control DGP – installed on the local bus.
Besides monitoring the choice of a floor by the user, the inputs can be used to monitor
the elevator, registering stopping/opening the elevator doors. Also in this case, the whole
input address range is needed.
Floor 64
Floor 63
Floor:
Floor:
Floor 5
Floor 6
Floor 4
Floor 3
Floor 2
Floor 1
Elevator 1
Reader 1
Input 64
Input 63
Input:
Input:
Input 5
Input 5
Input 4
Input 3
Input 2
Input 1
Floor buttons Access signal
Drawing 4-5 ATS1260 elevator control input and output diagram.
Mapping the inputs and outputs to a particular elevator can be found in Table 4-12.
Designing the local DGP is no different from designing the system bus devices. The
same devices as well as the same approach are used.